ANALYSIS OF THE
INFORMATION SUBMITTED ON MIS FORMATS BY MP POWER TRANSMISSION COMPANY LIMITED
FOR THE YEAR 2005-06.
TRANSCO-QUARTERLY MIS TRANSCO
Format Tr-1
The information on quantum of energy handled by the State Transmission
System and the overloading of lines for continuously 2 hours
|
|
SR. NO. |
Description |
Units |
Target
for the
Qtr 1 |
Actual
for the
Qtr 1 |
Target
for the
Qtr 2 |
Actual
for the
Qtr 2 |
Target
for the Qtr 3 |
Actual
for the
Qtr 3 |
Target
for the
Qtr 4 |
Actual
for the
Qtr 4 |
Target
for the YEAR |
Actual
for the YEAR |
Actual
for the last
year
(04-05) |
|
1 |
Total Energy Received at Interface Points_ MP
Periphery (ISGS + Bi-lateral+SSGS+Other
imports) |
MU |
7230.72 |
6588.47 |
7108.01 |
7050.21 |
9477.20 |
9533.27 |
7900.48 |
8130.07 |
31716.41 |
31302.02 |
29776.07 |
|
a |
Energy received from State Generators including
33 KV Direct Injection to Discoms |
MU |
3674.97 |
3168.40 |
3292.63 |
3265.85 |
4227.83 |
4252.35 |
3783.79 |
3872.63 |
14979.22 |
14559.23 |
15084.64 |
|
b |
33KV Direct injection of Discom from MP Genco |
MU |
68.79 |
63.31 |
67.58 |
67.04 |
81.39 |
81.39 |
67.85 |
78.93 |
285.61 |
290.67 |
264.73 |
|
c |
Energy Received from State Generators Excluding
33KV Direct injection to Discoms (a-b) |
MU |
3606.18 |
3105.09 |
3225.05 |
3198.81 |
3904.43 |
4170.96 |
3715.96 |
3793.70 |
14451.62 |
14268.56 |
14819.91 |
|
d |
Energy Received from other Generators Indira
Sagar |
MU |
138.2 |
160.81 |
1354.26 |
1343.24 |
611.97 |
653.75 |
510.16 |
397.95 |
2614.59 |
2555.75 |
1321.93 |
|
e |
Energy received from other sources
Pichhore-Matatila(UPSEB) |
MU |
1.27 |
1.07 |
2.95 |
2.93 |
9.07 |
9.69 |
7.56 |
4.11 |
20.85 |
17.80 |
29.78 |
|
f |
Energy Received at Interface points between
PGCIL & MPPTCL |
MU |
3481.07 |
3308.67 |
2494.80 |
2474.51 |
4369.46 |
4667.73 |
3642.51 |
3913.59 |
13987.84 |
14364.50 |
13339.72 |
|
g |
Energy Received from Wind farm,National Steel &
HEG |
MU |
4.00 |
12.82 |
25.46 |
25.26 |
22.82 |
24.38 |
19.02 |
14.64 |
71.30 |
77.10 |
|
|
h |
Energy Received from HEG Mandideep & JP Bela |
MU |
|
|
5.49 |
5.45 |
6.32 |
6.76 |
5.27 |
6.08 |
17.08 |
18.29 |
|
|
i |
Total Energy
Received at Interface Points excluding 33KV Direct injection from
MPPGCL(c+d+e+f+g+h) |
MU |
|
|
7108.01 |
7050.21 |
9477.20 |
9533.27 |
7900.48 |
8130.07 |
24485.69 |
24713.55 |
|
|
2 |
Total Energy
Sent to Discoms (Excluding 33KV Direct injection) |
MU |
6947.65 |
6365.10 |
6751.13 |
6551.39 |
8439.13 |
9015.20 |
7513.78 |
8051.14 |
29651.69 |
29982.83 |
28362.46 |
|
a |
Energy Sent to
Poorve Khestra |
MU |
2171.02 |
1976.17 |
2075.01 |
2013.62 |
2414.00 |
2439.13 |
2033.69 |
2232.29 |
8693.72 |
8661.21 |
8405.06 |
|
b |
Energy Sent to
Paschim Khestra |
MU |
2481.40 |
2297.16 |
2467.12 |
2394.13 |
3669.90 |
3709.67 |
3091.73 |
2875.81 |
11710.15 |
11276.77 |
9954.43 |
|
c |
Energy Sent to
Madhya Khestra |
MU |
2223.44 |
2026.08 |
2200.77 |
2135.66 |
2827.00 |
2858.43 |
2381.62 |
2567.74 |
9632.83 |
9587.91 |
10002.97 |
|
d. |
Energy Sent to
other Lincessee_SEZ Indore |
MU |
2.00 |
2.38 |
8.23 |
7.98 |
8.00 |
7.97 |
6.74 |
7.87 |
24.97 |
26.20 |
0.00 |
|
e |
Total Energy
Sent to Discoms (Excluding 33KV Direct injection from PH only) |
MU |
6877.86 |
6301.80 |
6751.13 |
6551.39 |
8918.90 |
9015.20 |
7513.78 |
7683.71 |
30061.67 |
29552.10 |
28097.73 |
|
3 |
Energy Export to
Rajasthan |
MU |
|
|
0.00 |
-187.32 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-187.32 |
1413.61 |
|
4 |
Energy Loss (1i-2e+3) |
MU |
351.86 |
286.67 |
356.88 |
311.49 |
558.30 |
518.07 |
386.70 |
446.36 |
1653.74 |
1562.59 |
|
|
5 |
Total
Transmission Loss((4x100/1i) |
% |
4.88% |
4.35% |
5.02 |
4.42 |
5.89 |
5.43 |
4.89 |
5.49 |
15.85 |
15.38 |
4.79 |
|
6 |
Line wise Losses |
|
|
|
|
|
|
|
|
|
0.00 |
0.00 |
|
|
a. |
Agregate of 400 kv lines |
% |
1.63 |
1.49 |
1.63 |
1.33 |
1.36 |
1.44 |
1.36 |
1.36 |
5.98 |
5.62 |
|
|
b. |
Agregate of 220 kv lines |
% |
3.06 |
2.88 |
3.06 |
2.92 |
3.55 |
3.57 |
3.55 |
3.49 |
13.22 |
12.86 |
|
|
c. |
Agregate of 132 kv lines |
% |
1.25 |
0.97 |
1.25 |
1.21 |
2.17 |
1.48 |
2.17 |
1.68 |
6.84 |
5.34 |
|
|
7 |
Name of top 10 lines with Max. congesation in
terms of MW for continuosly 2 hrs. |
|
|
% Over Loading
(#) |
|
% Over Loading
(#) |
|
% Over Loading
(#) |
|
% Over Loading
(#) |
|
% Over Loading
(#) |
|
|
a |
DAMOH-BIJAWAR 132KV |
|
|
232.00 |
|
224.00 |
|
232.00 |
|
236.00 |
|
236.00 |
|
|
|
BANMORE - MALANPUR 132 KV |
|
|
184.00 |
|
|
|
|
|
|
|
184.00 |
|
|
|
NARSINGPUR - GADARWARA 132 KV |
|
|
180.00 |
|
|
|
208.00 |
|
232.00 |
|
232.00 |
|
|
b |
BINA-GWALIOR-I 220KV |
|
|
|
|
196.97 |
|
196.97 |
|
206.00 |
|
206.00 |
|
|
c |
BINA-GWALIOR-II 220KV |
|
|
|
|
181.82 |
|
185.61 |
|
181.62 |
|
185.61 |
|
|
d |
INDORE-SOUTH- ZONE-II 220KV |
|
|
|
|
170.45 |
|
|
|
|
|
170.45 |
|
|
e |
INDORE-SOUTH- ZONE-I 220KV |
|
|
|
|
166.67 |
|
|
|
|
|
166.67 |
|
|
f |
MAHALGAON-MOTIJHEEL 132KV |
|
|
176.00 |
|
164.00 |
|
|
|
|
|
176.00 |
|
|
|
MAHALGAON - TIGRA 132 KV |
|
|
176.00 |
|
|
|
|
|
|
|
176.00 |
|
|
|
MAHALGAON - BINA 220 KV |
|
|
174.24 |
|
|
|
|
|
|
|
174.24 |
|
|
g |
PICHHORE-DATIA 132KV |
|
|
|
|
160.00 |
|
|
|
|
|
160.00 |
|
|
h |
DAMOH-GARHAKOTA 132KV |
|
|
|
|
160.00 |
|
|
|
|
|
160.00 |
|
|
I |
BINA-PICHHORE 132KV |
|
|
|
|
160.00 |
|
|
|
|
|
160.00 |
|
|
j |
PICHHORE-RAJGHAT 132KV |
|
|
176.00 |
|
160.00 |
|
188.00 |
|
200.00 |
|
200.00 |
|
|
|
PACHHORE - BINA 132 KV |
|
|
176.00 |
|
|
|
186.00 |
|
188.00 |
|
188.00 |
|
|
|
INDORE - UJJAIN II (JAITPURA) 220 KV |
|
|
166.67 |
|
|
|
|
|
|
|
166.67 |
|
|
|
SHUJALPUR - ARNIYAKALAN 132 KV |
|
|
|
|
|
|
186.00 |
|
182.00 |
|
186.00 |
|
|
|
BIJAWAR - TIKAMGARH 132 KV |
|
|
|
|
|
|
172.00 |
|
181.62 |
|
181.62 |
|
|
|
ITTARSI - BARWAHA - 220 KV |
|
|
162.88 |
|
|
|
181.82 |
|
181.62 |
|
181.82 |
|
|
|
GARHAKOTA - SAGAR 132 KV |
|
|
|
|
|
|
172.00 |
|
181.62 |
|
181.62 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(#)-
Calculated on the basis of "SIL" given in CERC Tariff Regulation dated
26.03.2004. |
|
|
Note - Figures
indicate at Sl.No. 2,3,4 & 5 are tentative. These figures may change after
finalization of regional energy accounts by WREB |